IEC 60038

{{Short description|Set of standard voltages}}

{{1R|date=March 2017}}{{Use British (Oxford) English|date=January 2012}}

{{IEC voltage ranges}}

International Standard IEC 60038, IEC standard voltages, defines a set of standard voltages for use in low voltage and high voltage AC and DC electricity supply systems.

Low voltage

Where two voltages are given below separated by "/", the first is the root-mean-square voltage between a phase and the neutral connector, whereas the second is the corresponding root-mean-square voltage between two phases (exception: the category shown below called "One Phase", where 240 V is the root-mean-square voltage between the two legs of a split phase). The three-phase voltages are for use in either four-wire (with neutral) or three-wire (without neutral) systems.

= Three-phase 50 Hz =

  • 230 V / 400 V (formerly 220/380 V)
  • 400 V / 690 V (formerly 380/660 V)
  • 1000 V phase to phase (3 wire)

Suppliers using 220 V / 380 V or 240 V / 415 V systems were expected by the standard to migrate to the recommended value of 230 V / 400 V by the year 2003. This migration has already been largely completed, at least within the European Union.

= Voltage conversion schedule =

class=wikitable

! Year !! Neutral-Phase [V] / Phase-Phase [V] !! Tolerances

— 1987220 V / 380 V– 10% .. + 10%
1988 — 2003230 V / 400 V– 10% .. + 6%
2003 —230 V / 400 V– 10% .. + 10%

= Three-phase 60 Hz =

  • 120 V / 208 V
  • 240 V
  • 230 V / 400 V
  • 277 V / 480 V
  • 480 V
  • 347 V / 600 V
  • 600 V / 1000 V

= One-phase, three-wire 60 Hz (American split-phase) =

  • 120 V / 240 V

Table 3 1 kV to 35 kV

Table 3 of IEC 60038 lists nominal voltages above 1 kV and not exceeding 35 kV. There are two series, one from 3 kV up to 35 kV

Table 4 35 kV - 230 kV

Table 4 shows nominal voltages above 35 kV and not exceeding 230 kV.

== Table 5 245 - 1,200 kV ==

Table 5 is systematically different, as the highest voltage for equipment is the characteristic value exceeding 245 kV. The enumeration begins at 300 kV and ends with 1200 kV.

See also

References

[https://archive.today/20130411020347/http://webcache.googleusercontent.com/search?q=cache:DortT_ULynsJ:http://www.automation.siemens.com/mcms/infocenter/dokumentencenter/sc/pp/Documentsu20Catalogs/E86060-K2410-A111-A8-7600_KT10_1_2012_en_kap_16.pdf%2B220 googleusercontent.com/siemens.com - Technical information and configuring notes], 2011