Variable-frequency drive

{{Short description|Type of adjustable-speed drive}}

{{Use mdy dates|date=May 2022}}

File:Small variable-frequency drive.jpg

File:HitachiJ100A.jpg

A variable-frequency drive (VFD, or adjustable-frequency drive, adjustable-speed drive, variable-speed drive, AC drive, micro drive, inverter drive, variable voltage variable frequency drive, or drive) is a type of AC motor drive (system incorporating a motor) that controls speed and torque by varying the frequency of the input electricity. Depending on its topology, it controls the associated voltage or current variation.{{cite book | first=Sylvester J. | last=Campbell | year=1987 | title=Solid-State AC Motor Controls | publisher=Marcel Dekker, Inc. | location=New York | isbn=978-0-8247-7728-9 | pages= 79–189 }}{{cite book|last=Jaeschke|first=Ralph L.|title=Controlling Power Transmission Systems|publisher=Penton/IPC|year=1978|isbn=978-1114762060|location=Cleveland, OH|pages=210–215}}{{cite book | first=Charles S. | last=Siskind | year=1963 | title=Electrical Control Systems in Industry | publisher=McGraw-Hill, Inc. | location=New York | isbn=978-0-07-057746-6 | page=[https://archive.org/details/electricalcontro0000unse/page/224 224] | url=https://archive.org/details/electricalcontro0000unse/page/224 }}{{cite book | last=NEMA Standards Publication | title=Application Guide for AC Adjustable Speed Drive Systems | year=2007 | url=https://www.nema.org/standards/view/application-guide-for-ac-adjustable-speed-drive-systems| access-date=March 27, 2008 | publisher=National Electrical Manufacturers Association | location=Rosslyn, VA USA | page=4}}{{Cite conference|url=https://site.ieee.org/sas-pesias/files/2016/03/Whats-New-with-Medium-Voltage-Drives_Slides.pdf|last1=Lockley|first1=William|last2=Paes|first2=Richard|title=What's New In Medium Voltage Drives|conference=IEEE SAS & NCS 2014 PES/IAS Joint Chapter Technical Seminar|year=2014|access-date =January 28, 2022|quote=Adjustable Speed Drive System: An interconnected combination of equipment that provides a means of adjusting the speed of a mechanical load coupled to a motor.|page=slide 91 of 132}}, quote is per definition on p. 4 of NEMA Standards Publication ICS 7.2-2021.

VFDs are used in applications ranging from small appliances to large compressors.{{Cite web|title=Medium Voltage Integrated Drive and Motor|url=https://www.energy.gov/sites/prod/files/2017/03/f34/Medium%20Voltage%20Integrated%20Drive%20and%20Motor_0.pdf|website=energy.gov – DoE|language=en-GB}} Systems using VFDs can be more efficient than hydraulic systems, such as in systems with pumps and damper control for fans.{{cite web|title=Energy efficiency makes a difference|url=http://www02.abb.com/db/db0003/db002698.nsf/0/a3881ed5c3dbc647c12575080036dafd/$file/energy_efficiency_makes_difference_191108.pdf|access-date=May 1, 2017|archive-url=https://web.archive.org/web/20170908185247/http://www02.abb.com/db/db0003/db002698.nsf/0/a3881ed5c3dbc647c12575080036dafd/$file/Energy_efficiency_makes_difference_191108.pdf|archive-date=September 8, 2017|url-status=dead}}

Since the 1980s, power electronics technology has reduced VFD cost and size and has improved performance through advances in semiconductor switching devices, drive topologies, simulation and control techniques, and control hardware and software.

VFDs include low- and medium-voltage AC–AC and DC–AC topologies.

History

Pulse-width modulation (PWM) variable-frequency drive projects started in the 1960s at Strömberg in Finland. {{Interlanguage link|Martti Harmoinen|fi}} is regarded as the inventor of this technology.{{Cite web |date=2023-06-20 |title=Muistokirjoitus {{!}} Martti Harmoinen 1934–2023 |url=https://www.hs.fi/muistot/art-2000009649557.html |access-date=2023-06-22 |website=Helsingin Sanomat |language=fi}}{{Cite web |title=Taajuusmuuttajasta tuli Suomen suuri innovaatio - IN0619 |url=https://insinoori-lehti.fi/digilehti/in0619/taajuusmuuttajasta-tuli-suomen-suuri-innovaatio |access-date=2023-06-22 |website=insinoori-lehti.fi |language=fi}}{{Cite web |title=Suomi100-innovaatiot, sija 5: taajuusmuuttaja |url=https://etn.fi/index.php/13-news/7240-suomi100-innovaatiot-sija-5-taajuusmuuttaja |access-date=2023-06-22 |website=etn.fi}} Strömberg managed to sell the idea of PWM drive to Helsinki Metro in 1973 and in 1982 the first PWM drive SAMI10 were operational.{{Cite web |date=2021-06-14 |title=Edelläkävijät osaavat lukea signaaleja ympärillään |url=https://trafiikki.fi/edellakavijat-osaavat-lukea-signaaleja-ymparillaan/ |access-date=2023-06-22 |website=Trafiikki |language=fi}}{{Cite web |title=Tekniikan Maailma |url=https://tekniikanmaailma.fi/sahkomoottorin-kaasupolkimen-suomalainen-isa-martti-harmoinen-on-poissa-helsingin-metrosta-tekniikka-levisi-teollisuuteen-sahkoautoihin-ja-hisseihin/ |access-date=2023-06-22 |website=tekniikanmaailma.fi}}{{Cite web |last=museo |first=Tekniikan |date=2021-07-15 |title=Esinekummi tekee näkyväksi tekniikan ja teollisuuden tarinaa |url=https://tekniikanmuseo.wordpress.com/2021/07/15/esinekummi-tekee-nakyvaksi-tekniikan-ja-teollisuuden-tarinaa/ |access-date=2023-06-22 |website=Tekniikan museo |language=fi}}

System description and operation

File:Variable-frequency Drive System.png

A variable-frequency drive is a device used in a drive system consisting of the following three main sub-systems: AC motor, main drive controller assembly, and drive/operator interface.{{rp|210–211}}

=AC motor=

The AC electric motor used in a VFD system is usually a three-phase induction motor. Some types of single-phase motors or synchronous motors can be advantageous in some situations, but generally three-phase induction motors are preferred as the most economical. Motors that are designed for fixed-speed operation are often used. Elevated-voltage stresses imposed on induction motors that are supplied by VFDs require that such motors be designed for definite-purpose inverter-fed duty in accordance with such requirements as Part 31 of NEMA Standard MG-1.NEMA Guide, p. 13

=Controller=

{{Further|FAM control of induction motor}}

The VFD controller is a solid-state power electronics conversion system consisting of three distinct sub-systems: a rectifier bridge converter, a direct current (DC) link, and an inverter. Voltage-source inverter (VSI) drives (see 'Generic topologies' sub-section below) are by far the most common type of drives. Most drives are AC–AC drives in that they convert AC line input to AC inverter output. However, in some applications such as common DC bus or solar applications, drives are configured as DC–AC drives. The most basic rectifier converter for the VSI drive is configured as a three-phase, six-pulse, full-wave diode bridge. In a VSI drive, the DC link consists of a capacitor which smooths out the converter's DC output ripple and provides a stiff input to the inverter. This filtered DC voltage is converted to quasi-sinusoidal AC voltage output using the inverter's active switching elements. VSI drives provide higher power factor and lower harmonic distortion than phase-controlled current-source inverter (CSI) and load-commutated inverter (LCI) drives (see 'Generic topologies' sub-section below). The drive controller can also be configured as a phase converter having single-phase converter input and three-phase inverter output.Campbell, pp. 79–83

Controller advances have exploited dramatic increases in the voltage and current ratings and switching frequency of solid-state power devices over the past six decades. Introduced in 1983,{{cite book|last=Bose|first=Bimal K.|title=Power Electronics and Motor Drives : Advances and Trends|url=https://archive.org/details/powerelectronics00bose_657|url-access=limited|year=2006|publisher=Academic|location=Amsterdam|isbn=978-0-12-088405-6|page=[https://archive.org/details/powerelectronics00bose_657/page/n39 22]}} the insulated-gate bipolar transistor (IGBT) has in the past two decades come to dominate VFDs as an inverter switching device.{{cite journal|last=Bartos|first=Frank J.|date=September 1, 2004|title=AC Drives Stay Vital for the 21st Century|url=https://www.controleng.com/articles/ac-drives-stay-vital-for-the-21st-century/|journal=Control Engineering}}{{cite conference | first =Robert E. | last = Eisenbrown | chapter= AC Drives, Historical and Future Perspective of Innovation and Growth | title = Keynote Presentation for the 25th Anniversary of The Wisconsin Electric Machines and Power Electronics Consortium (WEMPEC) | pages =6–10 | publisher =WEMPEC | date =May 18, 2008 | location = University of Wisconsin, Madison, WI, USA }}{{cite journal | last =Jahn | first =Thomas M. |author2=Owen, Edward L. | title =AC Adjustable-Speed Drives at the Millennium: How Did We Get Here? | journal =IEEE Transactions on Power Electronics | volume = 16 | issue = 1 | pages =17–25 | date =January 2001 | doi =10.1109/63.903985 | bibcode =2001ITPE...16...17J | url =http://digital.library.wisc.edu/1793/11120 }}

In variable-torque applications suited for Volts-per-Hertz (V/Hz) drive control, AC motor characteristics require that the voltage magnitude of the inverter's output to the motor be adjusted to match the required load torque in a linear V/Hz relationship. For example, for 460 V, 60 Hz motors, this linear V/Hz relationship is 460/60 = 7.67 V/Hz. While suitable in wide-ranging applications, V/Hz control is sub-optimal in high-performance applications involving low speed or demanding, dynamic speed regulation, positioning, and reversing load requirements. Some V/Hz control drives can also operate in quadratic V/Hz mode or can even be programmed to suit special multi-point V/Hz paths.{{cite web|title=Basics of AC drives|url=http://www3.sea.siemens.com/step/flash/STEPACDrives/index.htm|access-date=April 18, 2012|page=Hardware-Part 2: slide 2 of 9|archive-url=https://web.archive.org/web/20120419103737/http://www3.sea.siemens.com/step/flash/STEPACDrives/index.htm|archive-date=April 19, 2012|url-status=dead}}{{cite book | first=Bimal K. | last=Bose | year=1980 | title=Adjustable Speed AC Drive Systems | publisher=IEEE Press | location=New York | isbn=978-0-87942-146-5| bibcode=1981asad.book.....B }}

The two other drive control platforms, vector control and direct torque control (DTC), adjust the motor voltage magnitude, angle from reference, and frequency{{cite web|last=Yano|first=Masao|title=History of Power Electronics for Motor Drives in Japan|url=http://www.ieeeghn.org/wiki/images/4/49/Yano2.pdf|access-date=April 18, 2012|page=13|display-authors=etal|archive-date=June 2, 2012|archive-url=https://web.archive.org/web/20120602073342/http://www.ieeeghn.org/wiki/images/4/49/Yano2.pdf|url-status=dead}} so as to precisely control the motor's magnetic flux and mechanical torque.

Although space vector pulse-width modulation (SVPWM) is becoming increasingly popular,{{cite conference |date=June 8, 2012|url=https://ieeexplore.ieee.org/document/6214597|last=Bose |first=Bimal K. |title=Global Energy Scenario and Impact on Power Electronics In the 21st Century |conference=PEIA 2011 – Workshop on Power Electronics for Industrial Applications and Renewable Energy Conversion |page=12 |location=Doha, Qatar|access-date=February 8, 2012|publisher=IEEE}} sinusoidal PWM (SPWM) is the most straightforward method used to vary drives' motor voltage (or current) and frequency. With SPWM control (see Fig. 1), quasi-sinusoidal, variable-pulse-width output is constructed from intersections of a saw-toothed carrier signal with a modulating sinusoidal signal which is variable in operating frequency as well as in voltage (or current).Bose (2006), p. 183Campbell, pp. 82–85

Operation of the motors above rated nameplate speed (base speed) is possible, but is limited to conditions that do not require more power than the nameplate rating of the motor. This is sometimes called "field weakening" and, for AC motors, means operating at less than rated V/Hz and above rated nameplate speed. Permanent magnet synchronous motors have quite limited field-weakening speed range due to the constant magnet flux linkage. Wound-rotor synchronous motors and induction motors have much wider speed range. For example, a 100 HP, 460 V, 60 Hz, 1775 RPM (4-pole) induction motor supplied with 460 V, 75 Hz (6.134 V/Hz), would be limited to 60/75 = 80% torque at 125% speed (2218.75 RPM) = 100% power.Bose (1980), p. 3 At higher speeds, the induction motor torque has to be limited further due to the lowering of the breakaway torque{{efn|NEMA Guide defines a motor's breakaway torque as 'The torque that a motor produces at zero speed when operating on a control', and a motor's breakdown torque as 'The maximum torque that it will develop with rated voltage applied at rated frequency on sinewave power, without an abrupt drop in speed.'}} of the motor. Thus, rated power can be typically produced only up to 130–150% of the rated nameplate speed. Wound-rotor synchronous motors can be run at even higher speeds. In rolling mill drives, often 200–300% of the base speed is used. The mechanical strength of the rotor limits the maximum speed of the motor.

File:Pwm.png

An embedded microprocessor governs the overall operation of the VFD controller. Basic programming of the microprocessor is provided as user-inaccessible firmware. User programming of display, variable, and function block parameters is provided to control, protect, and monitor the VFD, motor, and driven equipment.Basics of AC Drives, p. Programming: slide 3 of 7

The basic drive controller can be configured to selectively include such optional power components and accessories as follows:

  • Connected upstream of converter – circuit breaker or fuses, isolation contactor, EMC filter, line reactor, passive filter
  • Connected to DC link – braking chopper, braking resistor
  • Connected downstream of inverter—output reactor, sine wave filter, dV/dt filter.{{efn|The mathematical symbol dV/dt, defined as the derivative of voltage V with respect to time t, provides a measure of rate of voltage rise, the maximum admissible value of which expresses the capability of capacitors, motors, and other affected circuit elements to withstand high current or voltage spikes due to fast voltage changes; dV/dt is usually expressed in V/microsecond.{{cite web|title=Film capacitors – Short Definition of Terms|url=http://www.epcos.com/web/generator/Web/Sections/ProductCatalog/Capacitors/FilmCapacitors/PDF/PDF__DefinitionOfTerms,property=Data__en.pdf;/PDF_DefinitionOfTerms.pdf|access-date=May 22, 2012|page=2|archive-date=September 5, 2012|archive-url=https://web.archive.org/web/20120905113706/http://www.epcos.com/web/generator/Web/Sections/ProductCatalog/Capacitors/FilmCapacitors/PDF/PDF__DefinitionOfTerms,property=Data__en.pdf;/PDF_DefinitionOfTerms.pdf|url-status=dead}}}}Basics of AC Drives, p. Hardware – Part 2: slide 7 of 9

=Operator interface=

The operator interface provides a means for an operator to start and stop the motor and adjust the operating speed. The VFD may also be controlled by a programmable logic controller through Modbus or another similar interface. Additional operator control functions might include reversing, and switching between manual speed adjustment and automatic control from an external process control signal. The operator interface often includes an alphanumeric display or indication lights and meters to provide information about the operation of the drive. An operator interface keypad and display unit is often provided on the front of the VFD controller as shown in the photograph above. The keypad display can often be cable-connected and mounted a short distance from the VFD controller. Most are also provided with input and output (I/O) terminals for connecting push buttons, switches, and other operator interface devices or control signals. A serial communications port is also often available to allow the VFD to be configured, adjusted, monitored, and controlled using a computer.{{cite journal | last =Cleaveland | first =Peter | title = AC Adjustable Speed Drives | journal =Control Engineering | date =November 1, 2007 }}Campbell, pp. 107–129

=Speed control=

There are two main ways to control the speed of a VFD; networked or hardwired. Networked involves transmitting the intended speed over a communication protocol such as Modbus, Modbus/TCP, EtherNet/IP, or via a keypad using Display Serial Interface while hardwired involves a pure electrical means of communication. Typical means of hardwired communication are: 4-20mA, 0-10VDC, or using the internal 24VDC power supply with a potentiometer. Speed control can be performed either remotely or locally, depending on the application's requirements. Remote control instructs the VFD to ignore speed commands from the keypad while local control instructs the VFD to ignore external control and only abide by the keypad.

= Programming a VFD =

Depending on the model a VFD's operating parameters can be programmed via: dedicated programming software, internal keypad, external keypad, or SD card. VFDs will often block out most programming changes while running. Typical parameters that need to be set include: motor nameplate information, speed reference source, on/off control source and braking control. It is also common for VFDs to provide debugging information such as fault codes and the states of the input signals.

Starting and software behavior

Most VFDs allow auto-starting, which will drive the output to a designated frequency after a power cycle, after a fault has been cleared, or after the emergency stop signal has been restored (generally emergency stops are active low logic). One popular way to control a VFD is to enable auto-start and place L1, L2, and L3 into a contactor. Powering on the contactor thus turns on the drive and has it output to a designated speed. Depending on the sophistication of the drive multiple auto-starting behavior can be developed e.g. the drive auto-starts on power up but does not auto-start from clearing an emergency stop until a reset has been cycled.

=Drive operation=

File:Four quadrant motion control of a motor.jpg

Referring to the accompanying chart, drive applications can be categorized as single-quadrant, two-quadrant, or four-quadrant; the chart's four quadrants are defined as follows:{{cite web|title=Technical guide No. 8 – Electrical Braking|url=https://library.e.abb.com/public/20be376000f34dd6b9c513580cf56423/Technical_guide_No_8_3AFE64362534_RevC.pdf|access-date=April 20, 2012}}{{cite web|title=Energy Regeneration|url=http://www.freescale.com/files/training_pdf/WBNR_ENERGY_REGENERATION.pdf|access-date=April 20, 2012}}Basics of AC Drives, pp. Hardware – Part 1: slides 9–10 of 11

  • Quadrant I – Driving or motoring,Energy Regeneration, slide 3 forward accelerating quadrant with positive speed and torque
  • Quadrant II – Generating or braking, forward braking-decelerating quadrant with positive speed and negative torque
  • Quadrant III – Driving or motoring, reverse accelerating quadrant with negative speed and torque
  • Quadrant IV – Generating or braking, reverse braking-decelerating quadrant with negative speed and positive torque.

Most applications involve single-quadrant loads operating in quadrant I, such as in variable-torque (e.g. centrifugal pumps or fans) and certain constant-torque (e.g. extruders) loads.

Certain applications involve two-quadrant loads operating in quadrant I and II where the speed is positive but the torque changes polarity as in case of a fan decelerating faster than natural mechanical losses. Some sources define two-quadrant drives as loads operating in quadrants I and III where the speed and torque is same (positive or negative) polarity in both directions.

Certain high-performance applications involve four-quadrant loads (Quadrants I to IV) where the speed and torque can be in any direction such as in hoists, elevators, and hilly conveyors. Regeneration can occur only in the drive's DC link bus when inverter voltage is smaller in magnitude than the motor back-EMF and inverter voltage and back-EMF are the same polarity.Energy Regeneration, slide 6

In starting a motor, a VFD initially applies a low frequency and voltage, thus avoiding high inrush-current associated with direct-on-line starting. After the start of the VFD, the applied frequency and voltage are increased at a controlled rate or ramped up to accelerate the load. This starting method typically allows a motor to develop 150% of its rated torque while the VFD is drawing less than 50% of its rated current from the mains in the low-speed range. A VFD can be adjusted to produce a steady 150% starting torque from standstill right up to full speed.Campbell, pp. 95–102 However, motor cooling deteriorates and can result in overheating as speed decreases such that prolonged low-speed operation with significant torque is not usually possible without separately motorized fan ventilation.

With a VFD, the stopping sequence is just the opposite as the starting sequence. The frequency and voltage applied to the motor are ramped down at a controlled rate. When the frequency approaches zero, the motor is shut off. A small amount of braking torque is available to help decelerate the load a little faster than it would stop if the motor were simply switched off and allowed to coast. Additional braking torque can be obtained by adding a braking circuit (resistor controlled by a transistor) to dissipate the braking energy. With a four-quadrant rectifier (active front-end), the VFD is able to brake the load by applying a reverse torque and injecting the energy back to the AC line.

Benefits

=Energy savings=

Many fixed-speed motor load applications that are supplied direct from AC line power can save energy when they are operated at variable speed by means of VFD. Such energy cost savings are especially pronounced in variable-torque centrifugal fan and pump applications, where the load's torque and power vary with the square and cube, respectively, of the speed. This change gives a large power reduction compared to fixed-speed operation for a relatively small reduction in speed. For example, at 63% speed a motor load consumes only 25% of its full-speed power. This reduction is in accordance with affinity laws that define the relationship between various centrifugal load variables.

In the United States, an estimated 60–65% of electrical energy is used to supply motors, 75% of which are variable-torque fan, pump, and compressor loads.{{cite journal|last=Bose|first=Bimal K.|title=The Past, Present, and Future of Power Electronics|journal=IEEE Industrial Electronics Magazine|date=June 2009|volume=3|issue=2|page=9|doi=10.1109/MIE.2009.932709}} Eighteen percent of the energy used in the 40 million motors in the U.S. could be saved by efficient energy improvement technologies such as VFDs.{{cite web|last=Spear|first=Mike|title=Adjustable Speed Drives: Drive Up Energy Efficiency|url=http://www.chemicalprocessing.com/articles/2005/489.html?page=1|publisher=ChemicalProcessing.com|access-date=January 27, 2012|archive-date=October 7, 2021|archive-url=https://web.archive.org/web/20211007080221/http://www.chemicalprocessing.com/articles/2005/489.html?page=1|url-status=dead}}{{cite journal|last=Bose|first=B. K.|title=Power Electronics and Motor Drives Recent Progress and Perspective|journal=IEEE Transactions on Industrial Electronics|date=February 2009|volume=56|issue=2|pages=581–588|doi=10.1109/tie.2008.2002726|s2cid=6139738}}

Only about 3% of the total installed base of AC motors are provided with AC drives.{{cite web|url=https://library.e.abb.com/public/d3c711ec2acddb18c125788f002cf5da/ABB_Technical_guide_No_4_REVC.pdf|title=Guide to Variable Speed Drives – Technical Guide No. 4|access-date=January 27, 2012}} However, it is estimated that drive technology is adopted in as many as 30–40% of all newly installed motors.{{cite web|last=Lendenmann|first=Heinz|title=Motoring Ahead|url=http://www.lead-central.com/AssetManager/02427e68-6f15-4f3a-9749-d37abf613741/Documents/APW2012/Low%20Voltage%20Drives%20Motors/ABB-136_WPO_Motoring%20ahead.pdf|access-date=April 18, 2012|display-authors=etal}}

An energy consumption breakdown of the global population of AC motor installations is as shown in the following table:

class="wikitable"

|+ Global population of motors, 2009{{cite web|last=Waide|first=Paul|author2=Brunner, Conrad U.|title=Energy-Efficiency Policy Opportunities for Electric Motor-Driven Systems|url=http://www.iea.org/publications/freepublications/publication/EE_for_ElectricSystems.pdf|publisher=International Energy Agency|year=2011|access-date=January 27, 2012|archive-date=August 10, 2017|archive-url=https://web.archive.org/web/20170810122020/http://www.iea.org/publications/freepublications/publication/EE_for_ElectricSystems.pdf|url-status=dead}}

!

! Small

! General Purpose – Medium-Size

! Large

Power

| 10 W – 750 W

| 0.75 kW – 375 kW

| 375 kW – 10000 kW

Phase, voltage

| 1-ph., <240 V

| 3-ph., 200 V to 1 kV

| 3-ph., 1 kV to 20 kV

% total motor energy

| 9%

| 68%

| 23%

Total stock

| 2 billion

| 230 million

| 0.6 million

=Control performance=

AC drives are used to bring about process and quality improvements in industrial and commercial applications' acceleration, flow, monitoring, pressure, speed, temperature, tension, and torque.Basics of AC drives, p. Overview: slide 5 of 6

Fixed-speed loads subject the motor to a high starting torque and to current surges that are up to eight times the full-load current. AC drives instead gradually ramp the motor up to operating speed to lessen mechanical and electrical stress, reducing maintenance and repair costs, and extending the life of the motor and the driven equipment.

Variable-speed drives can also run a motor in specialized patterns to further minimize mechanical and electrical stress. For example, an S-curve pattern can be applied to a conveyor application for smoother deceleration and acceleration control, which reduces the backlash that can occur when a conveyor is accelerating or decelerating.

Performance factors tending to favor the use of DC drives over AC drives include such requirements as continuous operation at low speed, four-quadrant operation with regeneration, frequent acceleration and deceleration routines, and need for the motor to be protected for a hazardous area.{{cite web|title=DC or AC Drives? A Guide for Users of Variable-Speed drives (VSDs)|url=http://www05.abb.com/global/scot/scot239.nsf/veritydisplay/046e0b4cdc2fe50ac1257466003a8443/$file/3adw000059.pdf|access-date=March 22, 2012|page=11}} The following table compares AC and DC drives according to certain key parameters:{{cite web|title=AC and DC Variable Speed Drives Application Considerations|url=http://www.reliance.com/prodserv/standriv/appnotes/d7725.pdf|access-date=March 22, 2012|page=2|archive-date=August 13, 2012|archive-url=https://web.archive.org/web/20120813032950/http://www.reliance.com/prodserv/standriv/appnotes/d7725.pdf|url-status=dead}}{{cite book|last=Drury|first=Bill|title=The Control Techniques Drives and Controls Handbook|url=https://archive.org/details/controltechnique00drur|url-access=limited|year=2009|publisher=Institution of Engineering and Technology|location=Stevenage, Herts, UK|isbn=978-1-84919-101-2|page=[https://archive.org/details/controltechnique00drur/page/n514 474]|edition=2nd}}{{cite web|last=Kang|first=Jun|title=General Purpose Permanent Magnet Motor Drive without Speed and Position Sensor|url=http://www.emsdrives.com/site/dmdrive.nsf/link2/NKOE-7U9HJG/$file/WP.AFD.05.pdf|access-date=September 7, 2012|archive-url=https://web.archive.org/web/20130718000207/http://www.emsdrives.com/site/dmdrive.nsf/link2/NKOE-7U9HJG/$file/WP.AFD.05.pdf|archive-date=July 18, 2013|url-status=dead}}

class="wikitable"
Drive typeDCAC VFDAC VFD || AC VFD || AC VFD
Control platformBrush type DCV/Hz controlVector controlVector control || Vector control
Control criteriaClosed-loopOpen-loopOpen-loopClosed-loop || Open-loop w. HFI^
MotorDCIMIMIM || Interior PM
Typical speed regulation (%)0.0110.50.010.02
Typical speed range at constant torque (%)0–10010–1003–1000–1000–100
Min. speed at 100% torque (% of base)Standstill8%2%StandstillStandstill (200%)
Multiple-motor operation recommendedNoYesNoNoNo
Fault protection (Fused only or inherent to drive)Fused onlyInherentInherentInherentInherent
Maintenance(Brushes)LowLowLowLow
Feedback deviceTachometer or encoderN/AN/AEncoderN/A

^ High-frequency injection

VFD types and ratings

=Generic topologies=

File:VSI Topology.jpg

File:CS Inverter Topology.jpg

File:6SWS.jpg

File:MC Topology.jpg

AC drives can be classified according to the following generic topologies:{{efn|A topology is defined in power electronics parlance as the relationship between AC drives' various elements.}}{{cite web|first=Ewan|last=Morris|author2=Armitage, David|title=A Guide to Standard Medium Voltage Variable Speed Drives, Part 2|url=https://library.e.abb.com/public/4fb66e46af347939c1256ed800338956/Fact%20Packs%20Part2.pdf|pages= 7–13|access-date=March 16, 2012}}{{cite journal|last=Paes|first=Richard|title=An Overview of Medium Voltage AC Adjustable Speed Drives and IEEE Std. 1566 – Standard for Performance of Adjustable Speed AC Drives Rated 375 kW and Larger|journal=Joint Power Engineering Society-Industrial Applications Society Technical Seminar|publisher=IEEE Southern Alberta Chapter|date=June 2011|pages= 1–78}}

  • Voltage-source inverter (VSI) drive topologies (see image): In a VSI drive, the DC output of the diode-bridge converter stores energy in the capacitor bus to supply stiff voltage input to the inverter. The vast majority of drives are VSI type with PWM voltage output.{{efn|The term PWM is often used to mean VSI-PWM, which is misleading as not only VSI drives are with PWM output.}}
  • Current-source inverter (CSI) drive topologies (see image): In a CSI drive, the DC output of the SCR-bridge converter stores energy in series-Inductor connection to supply stiff current input to the inverter. CSI drives can be operated with either PWM or six-step waveform output.
  • Six-step inverter drive topologies (see image):{{efn|The term six-step refers strictly speaking to an inverter waveform output alternative to PWM, some drives being configured as combined six-step and PWM options.}}{{cite journal|last=McMurray|first=William|title=Power Electronic Circuit Topology|journal=Proceedings of the IEEE|date=April 1988|volume=76|issue=4|pages=428–437|doi=10.1109/5.4428}} Now largely obsolete, six-step drives can be either VSI or CSI type and are also referred to as variable-voltage inverter drives, pulse-amplitude modulation (PAM) drives,{{cite book|last=Carrow|first=Robert S.|title=Electrician's Technical Reference: Variable Frequency Drives|year=2000|publisher=Delmar Thomson Learning|location=Albany, NY|isbn=978-0-7668-1923-8|pages=51}} square-wave drives or DC chopper inverter drives.Drury, p. 6 In a six-step drive, the DC output of the SCR-bridge converter is smoothed via capacitor bus and series-reactor connection to supply via Darlington Pair or IGBT inverter quasi-sinusoidal, six-step voltage or current input to an induction motor.{{citation |mode=cs1 |last=Sandy, Williams |author2=Baillie, Alastair |author3=Shipp, David |title=Understanding VSDs with ESPs – A Practical Checklist |publisher=Society of Petroleum Engineers |year=2003}}
  • Load commutated inverter (LCI) drive topologies: In an LCI drive (a special CSI case), the DC output of the SCR-bridge converter stores energy via DC link inductor circuit to supply stiff quasi-sinusoidal six-step current output of a second SCR-bridge's inverter and an over-excited synchronous machine. Low-cost SCR-thyristor-based LCI fed synchronous motor drives are often used in high-power low-dynamic-performance fan, pump and compressor applications rated up to 100 MW.{{cite book |last1=Wu |first1=B. |last2=Narimani |first2=Mehdi |title=High-power converters and AC drives |date=2017 |publisher=Wiley-IEEE Press |location=Hoboken, N.J. |isbn=9781119156031 |page=318 |edition=2nd|url=https://ieeexplore.ieee.org/book/7823162}} 480 pages, copyright 2017.
  • Cycloconverter or matrix converter (MC) topologies (see image): Cycloconverters and MCs are AC–AC converters that have no intermediate DC link for energy storage. A cycloconverter operates as a three-phase current source via three anti-parallel-connected SCR-bridges in six-pulse configuration, each cycloconverter phase acting selectively to convert fixed line-frequency AC voltage to an alternating voltage at a variable load frequency. MC drives are IGBT-based.
  • Doubly-fed slip recovery system topologies: A doubly-fed slip recovery system feeds rectified slip power to a smoothing reactor to supply power to the AC supply network via an inverter, the speed of the motor being controlled by adjusting the DC current.

=Control platforms=

{{See also|Dqo transformation|Alpha–beta transformation}}

Most drives use one or more of the following control platforms:Drury, pp. 6–9

=Load torque and power characteristics=

Variable-frequency drives are also categorized by the following load torque and power characteristics:

  • Variable torque, such as in centrifugal fan, pump, and blower applications
  • Constant torque, such as in conveyor and positive-displacement pump applications
  • Constant power, such as in machine tool and traction applications.

=Available power ratings=

VFDs are available with voltage and current ratings covering a wide range of single-phase and multi-phase AC motors. Low-voltage (LV) drives are designed to operate at output voltages equal to or less than 690 V. While motor-application LV drives are available in ratings of up to the order of 5 or 6 MW,{{cite web |title = ACS800, single drives, 0.55 to 5600 kW Catalog |work = ABB industrial drives |date = 2013 |url = https://library.e.abb.com/public/fcad7e1548b9e934c1257b67003616fe/EN_ACS800singledrivescatalogRevO.pdf}} economic considerations typically favor medium-voltage (MV) drives with much lower power ratings. Different MV drive topologies (see Table 2) are configured in accordance with the voltage/current-combination ratings used in different drive controllers' switching devices{{cite web|last=Wu|first=Bin|title=High-Power Converters and AC Drives|url=http://www.ee.ryerson.ca/~bwu/seminars/pesc05_seminar.pdf|publisher=IEEE PES|year=2005|access-date=February 3, 2012|page=slide 22}} such that any given voltage rating is greater than or equal to one to the following standard nominal motor voltage ratings: generally either {{frac|2|3|4}}.16 kV (60 Hz) or {{frac|3|3|6}}.6 kV (50 Hz), with one thyristor manufacturer rated for up to 12 kV switching. In some applications a step-up transformer is placed between a LV drive and a MV motor load. MV drives are typically rated for motor applications greater than between about {{convert|375| and |750|kW|hp|abbr=on}}. MV drives have historically required considerably more application design effort than required for LV drive applications.{{cite journal|last=Bartos | first =Frank J. | title =Medium-Voltage AC Drives Shed Custom Image | journal =Control Engineering | date =February 1, 2000 }}{{cite journal|last=Lockley|first=Bill |author2=Wood, Barry |author3=Paes, Richard |author4=DeWinter, Frank|title=Standard 1566 for (Un)Familiar Hands|journal=IEEE Industry Applications Magazine|date=Jan–Feb 2008|volume=14|issue=1|pages=21–28|doi=10.1109/MIA.2007.909800|s2cid=16455550 }} The power rating of MV drives can reach {{convert|100|MW|hp|abbr=on}}, a range of different drive topologies being involved for different rating, performance, power quality, and reliability requirements.Wu, slide 159

=Drives by machines and detailed topologies=

It is lastly useful to relate VFDs in terms of the following two classifications:

  • In terms of various AC machines as shown in Table 1 belowBose (2006) pp. Chapter 6–8, especially pp. 328, 397, 481{{cite web|title=Variable Speed Pumping, A Guide to Successful Applications, Executive Summary|url=http://www1.eere.energy.gov/industry/bestpractices/pdfs/variable_speed_pumping.pdf|publisher=USDOE – Europump – Hydraulic Institute|access-date=January 29, 2012|page=9, Fig. ES–7|date=May 2004|archive-url=https://web.archive.org/web/20111027042737/http://www1.eere.energy.gov/industry/bestpractices/pdfs/variable_speed_pumping.pdf|archive-date=October 27, 2011|url-status=dead}}
  • In terms of various detailed AC–AC converter topologies shown in Tables 2 and 3 below.{{cite book |doi=10.1109/EPE.2005.219669|chapter=High power medium voltage drives - innovations, portfolio, trends|title=2005 European Conference on Power Electronics and Applications|pages=10 pp.–P.10|year=2005|last1=Klug|first1=R.-D.|last2=Klaassen|first2=N.|isbn=90-75815-09-3|s2cid=15001359}}{{cite web|title=TMEiC Medium Voltage Drive Evolution|url=https://www.tmeic.com/sites/default/files/assets/files/library/MV%20Drive%20Evolution%20Brochure-2019web.pdf|access-date=February 3, 2012}}Wu, Slide 159{{cite book|editor-last=Rashid|editor-first=Muhammad H.|title=Power Electronics Handbook: Devices, Circuits, and Applications|url=https://archive.org/details/powerelectronics00rash_987|url-access=limited|year=2006|publisher=Academic|location=Burlington, MA|isbn=978-0-12-088479-7|page=[https://archive.org/details/powerelectronics00rash_987/page/n887 903]|edition=2nd}}{{cite journal |author1=J. Rodriguez |author2=Jih-Sheng Lai |author3=Fang Zheng Peng |title=Multilevel Inverters: A Survey of Topologies, Controls, and Applications|journal=IEEE Transactions on Industrial Electronics|volume=49|issue=4|pages=724–738|doi=10.1109/TIE.2002.801052|year=2002|hdl=10533/173647|hdl-access=free}}{{cite web|last=Ikonen|first=Mika|title=Two-Level and Three-Level Converter Comparison in Wind Power Application|year=2005|url=http://www.elkraft.ntnu.no/smola2005/Topics/15.pdf |archive-url=https://web.archive.org/web/20090419113306/http://www.elkraft.ntnu.no/smola2005/Topics/15.pdf |archive-date=April 19, 2009 |website=Institutt for elkraftteknikk |display-authors=etal}}{{cite journal|last=Kouro|first=Samir|author2=Rodriguez, Jose |author3=Wu, Bin |author4=Bernet, Steffen |author5= Perez, Marcelo |title=Powering the Future of Industry: High-Power Adjustable Speed Drive Topologies|journal=IEEE Industry Applications Magazine|date=Jul–Aug 2012|volume=18|issue=4|pages=26–39|doi=10.1109/MIAS.2012.2192231|s2cid=5825955}}

{{hidden begin|border=1px #aaa solid|title={{center|Table 1: Drives by machines}}}}

{{clade

|label1=Machines

|1={{clade

|label1=Induction^^^

|1={{clade

|label1=Cage rotor

|1={{clade

|1=CSI or VSI (six-step or PWM), cycloconverter, matrix

}}

|label2=WRIM

|2={{clade

|1=Electro-mechanical

}}

|label3=Doubly fed WRIM

|3={{clade

|1=Slip energy recovery (Kramer/Scherbius)

}}

}}

|label2=Synchronous^^^

|2={{clade

|label1=WFSM

|1={{clade

|1=CSI (LCI), cycloconverter, VSI

}}

|label2=PM

|2={{clade

|1=Axial or disk

|label2=Radial

|2={{clade

|1=Interior

|label2=Surface

|2={{clade

|label1=Trapezoidal BLDM, Sinusoidal PMSM

|1={{clade

|1=VSI

}}

}}

}}

}}

|label3=SyRM

|3={{clade

|1=VSI

}}

}}

|label3=VRM^^^

|3={{clade

|label1=Switched reluctance motor, Stepper motor

|1={{clade

|1=VSI

}}

}}

}}

}}

{{hidden end}}

{{hidden begin|border=1px #aaa solid|title={{center|Table 2: Drives by detailed AC–AC converter topologies }}}}

{{clade

|1=Topologies

|label2=Indirect AC–AC

|2={{clade

|label1=LV

|1={{clade

|label1=IGBT^

|1={{clade

|label1=2-level VSI PWM

|1={{clade

|1= Great majority of LV drive makes

}}

|label2=3-level VSI PWM

|2={{clade

|1= Primarily Yaskawa

}}

}}

|label2=(SCR/CSI or diode/VSI)+IGBT

|2={{clade

|label1=Six-step or PAM

|1={{clade

|1= For example Baker-Hughes

}}

}}

}}

|label2=MV

|2={{clade

|label1=VSI

|1={{clade

|label1=GCT^

|1={{clade

|label1=3-level NPC inverter

|1={{clade

|1= Primarily ABB, GE

}}

}}

|label2=IGBT^

|2={{clade

|label1=2-level inverter

|1={{clade

|1=Primarily GE-Converteam

}}

|label2=3-level NPC inverter

|2={{clade

|1=Primarily Eaton, GE-Toshiba, Siemens

}}

|label3=Multilevel CHB inverter

|3={{clade

|1=Primarily GE, Siemens (Robicon), Toshiba

}}

|label4=Flying-capacitor inverter drive

|4={{clade

|1=Primarily GE-Converteam

}}

|label5=NPC/H-bridge inverter drive

|5={{clade

|1=Primarily Toshiba

}}

}}

}}

|label2=CSI

|2={{clade

|label1= Primarily ABB, GE-Converteam, Siemens

|1={{clade

|label1=SCR^^

|1={{clade

|1=LCI

}}

}}

|label2=Primarily A-B

|2={{clade

|label1=SGCT^^ with AFE

|1={{clade

|1= CSR PWM / CSI PWM inverter with CME

}}

|label2=SCR + SGCT

|2={{clade

|1= 18-pulse CSI PWM drive

}}

|label3=GTO^^

|3={{clade

|1= Capacitor assisted CSI PWM drive (legacy)

}}

}}

}}

}}

}}

|label3=Direct AC–AC

|3={{clade

|label1=SCR

|1={{clade

|label1=Cycloconverter

|1={{clade

|1=Primarily ABB, Siemens, GE Converteam

}}

}}

|label2=IGBT

|2={{clade

|label1=Matrix

|1={{clade

|1=Primarily Yaskawa

}}

}}

}}

}}

{{hidden end}}

{{hidden begin|border=1px #aaa solid|title={{center|Table 3: Topology diagrams}}}}

File:2LI Topology.svg|Simplified 2-Level Inverter Topology

File:3LI Topology.jpg|Simplified Neutral Point Clamped 3-Level Inverter Topology

File:CHBI Topology.jpg|Simplified Cascaded H-bridge Inverter Topology

File:FCI Topology.jpg|Simplified Flying Capacitor Inverter 4-Level Topology

File:NPC-HBI Topology.jpg|Simplified Neutral Point Clamped H-bridge Inverter Topology

{{hidden end}}

{{hidden begin|border=1px #aaa solid|title={{center|Legend for Tables 1 to 3}}}}

class="wikitable"|style=font-size:50%;line-height:50%
^Inverter switching device (with std. diode rectifier)
^^Inverter and rectifier switching device
^^^Rotating or linear
AFEActive front end
BLDMPM trapezoid machine (Brushless DC electric motor)
CMECommon mode elimination
CHBCascaded H-bridge
CSICurrent source inverter
CSRCurrent source rectifier
GCTGate-controlled thyristor
GTOGate turn-off thyristor
IGBTInsulated gate bipolar transistor
LCILoad commutated inverter
LVLow voltage
MVMedium voltage
NPCNeutral point clamped
PAMPulse-amplitude modulation
PMPermanent magnet
PMSMPermanent magnet synchronous generator
PWMPulse-width modulation
SCRSilicon-controlled rectifier
SGCTSymmetrical gate controlled thyristor
SRMSwitched reluctance motor
SyRMSynchronous reluctance machine
VRMVariable-reluctance machine
VSIVoltage source inverter
VVIVariable-voltage inverter
WFSMWound-field synchronous machine
WRIMWound-rotor induction motor

{{hidden end}}

Application considerations

=AC line harmonics=

Note of clarification:.{{efn|The harmonics treatment that follows is limited for simplication reasons to LV VSI-PWM drives.}}

While harmonics in the PWM output can easily be filtered by carrier-frequency-related filter inductance to supply near-sinusoidal currents to the motor load, the VFD's diode-bridge rectifier converts AC line voltage to DC voltage output by super-imposing non-linear half-phase current pulses thus creating harmonic current distortion, and hence voltage distortion, of the AC line input. When the VFD loads are relatively small in comparison to the large, stiff power system available from the electric power company, the effects of VFD harmonic distortion of the AC grid can often be within acceptable limits. Furthermore, in low-voltage networks, harmonics caused by single-phase equipment such as computers and TVs are partially cancelled by three-phase diode bridge harmonics because their 5th and 7th harmonics are in counterphase.{{cite journal|last=Janssen|first=Hansen|author2=Neilsen, Peter |author3=Blaabjerg, Frede |title=Harmonic Cancellation by Mixing Non-Linear Single-Phase and Three-Phase Loads|journal=IEEE Transactions on Industry Applications|date=Jan–Dec 2000|volume=36|issue=1}} However, when the proportion of VFD and other non-linear load compared to total load or of non-linear load compared to the stiffness at the AC power supply, or both, is relatively large enough, the load can have a negative impact on the AC power waveform available to other power company customers in the same grid.

When the power company's voltage becomes distorted due to harmonics, losses in other loads such as normal fixed-speed AC motors are increased. This condition may lead to overheating and shorter operating life. Also, substation transformers and compensation capacitors are affected negatively. In particular, capacitors can cause resonance conditions that can unacceptably magnify harmonic levels. To limit the voltage distortion, owners of VFD load may be required to install filtering equipment to reduce harmonic distortion below acceptable limits. Alternatively, the utility may adopt a solution by installing filtering equipment of its own at substations affected by the large amount of VFD equipment being used. In high-power installations, harmonic distortion can be reduced by supplying multi-pulse rectifier-bridge VFDs from transformers with multiple phase-shifted windings.{{cite web | title = Guide to Harmonics with AC Drives – Technical Guide No. 6 |website=ABB | date =May 17, 2002 | url =http://www05.abb.com/global/scot/scot201.nsf/veritydisplay/6dff3290e5f2d651c125788d00393a58/$file/ABB_Technical%20guide%20No.6_REVC.pdf |archive-url=https://web.archive.org/web/20110626081829/http://www05.abb.com/global/scot/scot201.nsf/veritydisplay/6dff3290e5f2d651c125788d00393a58/$file/ABB_Technical%20guide%20No.6_REVC.pdf |archive-date=June 26, 2011 | access-date =July 29, 2009}}

It is also possible to replace the standard diode-bridge rectifier with a bi-directional IGBT switching device bridge mirroring the standard inverter which uses IGBT switching device output to the motor. Such rectifiers are referred to by various designations including active infeed converter (AIC), active rectifier, IGBT supply unit (ISU), active front end (AFE), or four-quadrant operation. With PWM control and a suitable input reactor, an AFE's AC line current waveform can be nearly sinusoidal. AFE inherently regenerates energy in four-quadrant mode from the DC side to the AC grid. Thus, no braking resistor is needed, and the efficiency of the drive is improved if the drive is frequently required to brake the motor.

Two other harmonics mitigation techniques exploit use of passive or active filters connected to a common bus with at least one VFD branch load on the bus. Passive filters involve the design of one or more low-pass LC filter traps, each trap being tuned as required to a harmonic frequency (5th, 7th, 11th, 13th, . . . kq+/-1, where k=integer, q=pulse number of converter).{{cite book |doi=10.1109/IEEESTD.1993.114370|publisher=IEEE|isbn=978-0-7381-0915-2|title=IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems }}

It is very common practice for power companies or their customers to impose harmonic distortion limits based on IEC or IEEE standards. For example, IEEE Standard 519 limits at the customer's connection point call for the maximum individual frequency voltage harmonic to be no more than 3% of the fundamental and call for the voltage total harmonic distortion (THD) to be no more than 5% for a general AC power supply system.IEEE 519, pp. 69–70

=Switching frequency foldback=

One drive uses a default switching frequency setting of 4 kHz. Reducing the drive's switching frequency (the carrier-frequency) reduces the heat generated by the IGBTs.ABB [https://library.e.abb.com/public/583ed5f1aa2c4723b325c1473dbaabcb/ACH550-PHPB01U-EN_REVD.pdf ACH550 Switching Frequency Foldback]

A carrier frequency of at least ten times the desired output frequency is used to establish the PWM switching intervals. A carrier frequency in the range of 2,000 to 16,000 Hz is common for LV [low voltage, under 600 Volts AC] VFDs. A higher carrier frequency produces a better sine wave approximation but incurs higher {{ill|switching loss|lt=switching losses|de|Schaltverluste}} in the IGBT, decreasing the overall power conversion efficiency.{{cite conference|last1=D'Aversa |first1=A. |last2=Hughes |first2=B. |last3=Patel |first3=S. |title=Challenges and solutions of protecting variable speed drive motors |conference=2013 66th Annual Conference for Protective Relay Engineers |date=April 8–11, 2013|page=2 |doi=10.1109/CPRE.2013.6822040 |url=https://cms-cdn.selinc.com/assets/Literature/Publications/Technical%20Papers/6596_ChallengesSolutions_BH_20130211_Web.pdf?v=20190111-001336| publisher =IEEE}}, pp. 250-256.

=Noise smoothing=

Some drives have a noise smoothing feature that can be turned on to introduce a random variation to the switching frequency. This distributes the acoustic noise over a range of frequencies to lower the peak noise intensity.

=Long-lead effects=

The carrier-frequency pulsed output voltage of a PWM VFD causes rapid rise times in these pulses, the transmission line effects of which must be considered. Since the transmission-line impedance of the cable and motor are different, pulses tend to reflect back from the motor terminals into the cable. The resulting reflections can produce overvoltages equal to twice the DC bus voltage or up to 3.1 times the rated line voltage for long cable runs, putting high stress on the cable and motor windings, and eventual insulation failure. Insulation standards for three-phase motors rated 230 V or less adequately protect against such long-lead overvoltages. On 460 V or 575 V systems and inverters with 3rd-generation 0.1-microsecond-rise-time IGBTs, the maximum recommended cable distance between VFD and motor is about 50 m or 150 feet. For emerging SiC MOSFET powered drives, significant overvoltages have been observed at cable lengths as short as 3 meters.{{Cite news|url=https://dvdtfilter.com/dv-dt-simulation-scenario-1-sic-drive/|title=dv/dt Simulation Scenario 1: SiC Drive – dv/dt Simulation and Mitigation|date=August 16, 2018|work=dv/dt Simulation and Mitigation|access-date=October 18, 2018|language=en-US}} Solutions to overvoltages caused by long lead lengths include minimizing cable length, lowering carrier frequency, installing dV/dt filters, using inverter-duty-rated motors (that are rated 600 V to withstand pulse trains with rise time less than or equal to 0.1 microsecond, of 1,600 V peak magnitude), and installing LCR low-pass sine wave filters.Skibinski, p. 274{{cite web|last=Novak|first=Peter|title=The Basics of Variable-Frequency Drives|url=http://ecmweb.com/power_quality/variable-frequency-drives-20090501/|publisher=EC&M|access-date=April 18, 2012|date=May 1, 2009|archive-date=April 13, 2012|archive-url=https://web.archive.org/web/20120413025214/http://ecmweb.com/power_quality/variable-frequency-drives-20090501/|url-status=dead}}{{cite journal|last=Finlayson|first=P.T.|title=Output filters for PWM drives with induction motors|date=Jan–Feb 1998|volume=4|issue=1|pages=46–52|journal=IEEE Industry Applications Magazine|doi=10.1109/2943.644886|s2cid=25469484}}{{Cite news|url=https://dvdtfilter.com/motor-voltage-waveform-simulation/|title=Motor Voltage Waveform Simulation - dv/dt Simulation and Mitigation|work=dv/dt Simulation and Mitigation|access-date=October 18, 2018|language=en-US}} Selection of optimum PWM carrier frequency for AC drives involves balancing noise, heat, motor insulation stress, common-mode voltage-induced motor bearing current damage, smooth motor operation, and other factors. Further harmonics attenuation can be obtained by using an LCR low-pass sine wave filter or dV/dt filter.{{cite book|doi=10.1109/PCICON.2004.1352810|publisher=IEEE|isbn=978-0-7803-8698-3 |pages = 269–278|year = 2004|last1 = Skibinski|first1 = G.|last2 = Breit|first2 = S.|title=IEEE Geoscience and Remote Sensing Letters |chapter=Line and load friendly drive solutions for long length cable applications in electrical submersible pump applications |s2cid=8945509}}{{cite web|title=Application Report Long Drive/Motor Leads|url=https://www.yaskawa.com/pycprd/download/search/detail?n=AR.AFD.05|access-date=February 14, 2012}}{{cite book|last=Malfait|first=A.|author2=Reekman, R. |author3=Belmans, R. |title=Proceedings of 1994 IEEE Industry Applications Society Annual Meeting |chapter=Audible noise and losses in variable speed induction motor drives with IGBT inverters-influence of the squirrel cage design and the switching frequency |year=1994|pages=693–700|doi=10.1109/IAS.1994.345435 |isbn=0-7803-1993-1 |s2cid=110917173 }}{{cite web|title=Who Cares About Carrier Frequency?|url=http://www.reliance.com/pdf/drives/data_sheets/D7171D.pdf|access-date=February 15, 2012|archive-date=July 11, 2014|archive-url=https://web.archive.org/web/20140711223237/http://www.reliance.com/pdf/drives/data_sheets/D7171D.pdf|url-status=dead}}

=Motor bearing currents=

{{Main|Shaft voltage}}

Carrier frequencies above 5 kHz are likely to cause bearing damage unless protective measures are taken.{{Cite web|url=http://www.nrel.gov/docs/fy13osti/56011.pdf|title=Minimize Adverse Motor and Adjustable Speed Drive Interactions | Advanced Manufacturing Office Energy Efficiency and Renewable Energy | U.S. Department of Energy}}

PWM drives are inherently associated with high-frequency common-mode voltages and currents which may cause trouble with motor bearings.{{cite journal|url=http://www.plantservices.com/articles/2007/022.html|pages=1–2|title=Bearings and Electricity Don't Match|year=2007|journal=PlantServices.com [Plant Services]|publisher=PtmanMedia|last=Yung|first=Chuck|location=Itasca, IL|access-date=April 16, 2008|archive-date=August 7, 2012|archive-url=https://web.archive.org/web/20120807214149/http://www.plantservices.com/articles/2007/022.html|url-status=dead}} When these high-frequency voltages find a path to earth through a bearing, transfer of metal or electrical discharge machining (EDM) sparking occurs between the bearing's ball and the bearing's race. Over time, EDM-based sparking causes erosion in the bearing race that can be seen as a fluting pattern. In large motors, the stray capacitance of the windings provides paths for high-frequency currents that pass through the motor shaft ends, leading to a circulating type of bearing current. Poor grounding of motor stators can lead to shaft-to-ground bearing currents. Small motors with poorly grounded driven equipment are susceptible to high-frequency bearing currents.{{cite web | title = Bearing Currents in Modern AC Drive Systems – Technical Guide No. 5 |website=ABB | date =December 1, 1999 | url =http://www05.abb.com/global/scot/scot201.nsf/veritydisplay/8c253c2417ed0238c125788f003cca8e/$file/abb_technical_guide_no5_revc.pdf |archive-url=https://web.archive.org/web/20110720013656/http://www05.abb.com/global/scot/scot201.nsf/veritydisplay/8c253c2417ed0238c125788f003cca8e/$file/abb_technical_guide_no5_revc.pdf |archive-date=July 20, 2011 | access-date =June 14, 2011}}

Prevention of high-frequency bearing current damage uses three approaches: good cabling and grounding practices, interruption of bearing currents, and filtering or damping of common-mode currents through common mode chokes. Good cabling and grounding practices can include use of shielded, symmetrical-geometry power cable to supply the motor, installation of shaft grounding brushes, and conductive bearing grease. Bearing currents can be interrupted by installation of insulated bearings and specially designed electrostatic-shielded induction motors. Filtering and damping high-frequency bearing can be done though inserting soft magnetic cores over the three phases giving a high frequency impedance against the common mode or motor bearing currents. Another approach is to use instead of standard 2-level inverter drives, using either 3-level inverter drives or matrix converters.{{cite book |pages=XLV–LVI, Fig. 16|publisher=IEEE|doi=10.1109/OPTIM.2008.4602333|chapter=Present state and a futuristic vision of motor drive technology|title=2008 11th International Conference on Optimization of Electrical and Electronic Equipment|year=2008|last1=Mahesh Swamy|last2=Tsuneo Kume|isbn=978-1-4244-1544-1|s2cid=39690131}}

=Dynamic braking=

{{See also|Dynamic braking|Regenerative braking}}

Torque generated by the drive causes the induction motor to run at synchronous speed less the slip. If the load drives the motor faster than synchronous speed, the motor acts as a generator, converting mechanical power back to electrical power. This power is returned to the drive's DC link element (capacitor or reactor). A DC-link-connected electronic power switch or braking DC chopper controls dissipation of this power as heat in a set of resistors. Cooling fans may be used to prevent resistor overheating.

Dynamic braking wastes braking energy by transforming it to heat. By contrast, regenerative drives recover braking energy by injecting this energy into the AC line. The capital cost of regenerative drives is, however, relatively high.{{Cite web|url=https://library.e.abb.com/public/20be376000f34dd6b9c513580cf56423/Technical_guide_No_8_3AFE64362534_RevC.pdf|title=Technical Guide No. 8, pp. 26–30}}

=Regenerative drives=

File:KIMO TRA U2 mL Gruppe.jpg

File:2010 Prius Regeneration.jpg

Regenerative AC drives have the capacity to recover the braking energy of a load moving faster than the designated motor speed (an overhauling load) and return it to the power system.{{Cite web |title=Reliance Electric FlexPak 3000 20FR4042 {{!}} Automation Industrial |url=https://20fr4042.com/blog |access-date=2023-12-09 |website=20fr4042.com |language=en}}

Cycloconverter, Scherbius, matrix, CSI, and LCI drives inherently allow return of energy from the load to the line, while voltage-source inverters require an additional converter to return energy to the supply.{{cite book|last=Dubey|first=Gopal K.|title=Fundamentals of Electrical Drives|year=2001|publisher=Alpha Science Int.|location=Pangbourne|isbn=978-1-84265-083-7|edition=2}}Rashid, p. 902, Table 33.13

Regeneration is useful in VFDs only where the value of the recovered energy is large compared to the extra cost of a regenerative system, and if the system requires frequent braking and starting. Regenerative VFDs are widely used where speed control of overhauling loads is required.Campbell, pp. 70–190

Some examples:

  • Conveyor belt drives for manufacturing, which stop every few minutes. While stopped, parts are assembled; once that is done, the belt moves on.
  • A crane, where the hoist motor stops and reverses frequently, and braking is required to slow the load during lowering.
  • Plug-in and hybrid electric vehicles of all types (see image and Hybrid Synergy Drive).