A power distribution unit (PDU) is a device fitted with multiple outputs designed to distribute electric power, especially to racks of computers and networking equipment located within a data center.{{Cite web|title=Definition of: Power distribution unit|url=https://www.pcmag.com/encyclopedia/term/60095/power-distribution-unit|publisher=Ziff Davis|work=PCMag.com|accessdate=March 8, 2014}} Data centers face challenges in power protection and management solutions. This is why many data centers rely on PDU monitoring to improve efficiency, uptime, and growth.{{Cite web|url=http://www.servertech.com/products/sentry-power-manager|title=Sentry Power Manager: Rack-Level Data Center Power Monitoring and Management|website=ServerTech.com|publisher=Server Technology|year=2014|accessdate=January 1, 2015}}{{Cite web |title=Benefits of intelligent power distribution |url=https://www.vertiv.com/en-us/about/news-and-insights/articles/educational-articles/benefits-of-intelligent-power-distribution/ |access-date=2023-12-29 |website=www.vertiv.com |language=en}} For data center applications, the power requirement is typically much larger than a home or office style power strips with power inputs as large as 22 kVA or even greater. Most large data centers utilize PDUs with 3-phase power input and 1-phase power output. There are two main categories of PDUs: Basic PDUs and Intelligent (networked) PDUs or iPDUs. Basic PDUs simply provide a means of distributing power from the input to a plurality of outlets. Intelligent PDUs normally have an intelligence module that allow the PDU for remote management of power metering information, power outlet on/off control, and/or alarms. Some advanced PDUs allow users to manage external sensors such as temperature, humidity, airflow, etc.
Form factors
PDUs vary from simple and inexpensive rack-mounted power strips to larger floor-mounted PDUs with multiple functions including power filtering to improve power quality, intelligent load balancing, and remote monitoring and control by LAN or SNMP. This kind of PDU placement offers intelligent capabilities such as power metering at the inlet, outlet, and PDU branch circuit level{{Cite web|url=https://www.raritan.com/products/feature/pdu-metering-at-the-inlet-outlet-and-branch-circuits|title=PDU Metering at the Inlet, Outlet, and Branch Circuits - Raritan|website=Raritan.com|year=2015|accessdate=May 25, 2015}} and support for environment sensors.{{Cite web|url= https://www.raritan.com/products/power/power-distribution/rack-pdu|title=Rack PDU - Rack Power Distribution - Intelligent PDU|website=Raritan.com|year=2015|accessdate=May 26, 2015}}
Newer generation of intelligent PDUs allow for IP consolidation, which means many PDUs can be linked in an array under a single IP address. Next-generation models also offer integration with electronic locks, providing the ability to network and manage PDUs and locks through the same appliance.{{cite patent|country=US|title=Systems and methods for controlling an electronic lock for a remote device|pubdate=January 9, 2018|inventor-last=Roth|inventor2-last=Conner|inventor3-last=Orris|inventor-first=Wayne D.|inventor2-first=Donald A.|inventor3-first=Ronald S.|number=9865109}}
In data centers, larger PDUs are needed to power multiple server cabinets. Each server cabinet or row of cabinets may require multiple high current circuits, possibly from different phases of incoming power or different UPSs. Standalone cabinet PDUs are self-contained units that include main circuit breakers, individual circuit breakers, and power monitoring panels. The cabinet provides internal bus bars for neutral and grounding. Prepunched top and bottom panels allow for safe cable entry.{{cite web | url=http://www.apc.com/products/family/index.cfm?id=367 | title=Cabinet Power Distribution | publisher=APC | accessdate=November 4, 2013}}